The formula used to calculate motor horsepower is straight forward:
Horsepower (3 phase) = (Volts x Amps x Efficiency x 1.732 x Power Factor) ÷ 746
If the above 50 hp motor is operating at 466 volts and drawing 43 amps (average across each of the 3 electrical leads), the fan’s operating horsepower can be calculated:
(466 Volts x 43 Amps x 1.732 x 0.945 Efficiency x 0.85 Power Factor) ÷ 746 = 37.37 Horsepower
Note that this result includes the fan’s drive losses (bearings and v-belt drive/or coupling). Using the following variation of the fan laws, this information can be helpful in determining how much the fan’s speed can be increased within the limitations of the electrical systems and how much additional flow the fan can produce.
RPMnew = 3√(Horespowernew ÷ Horespowerold) x RPMold
CFMnew = RPMnew ÷ RPMold
If the existing fan is currently moving 20,000 CFM, generating 10” SP, consuming 37.37 horsepower, operating at 1300 rpm and has a maximum operating speed of 1500 rpm, how much additional flow can it produce if the 50 horsepower motor is maxed out:
3√(50 Horsepowernew ÷ 37.37 Horespowerold) x 1,300 RPMold = 1,432 RPMnew
Since the speed is less than 1500 RPM, we can calculate out the new flow and pressure:
1,432 RPMnew ÷ 1,300 RPMold = 22,031 CFMnew
(1,432 RPMnew ÷ 1,300 RPMold)2 x 10” SP = 12” SP